Model |
DHC-E 8 |
DHC-E 10 |
Phase |
1 |
1 |
Voltage |
V |
208 |
240 |
208 |
240 |
Wattage |
kW |
5.4 |
7.2 |
7.2 |
9.6 |
Amperage |
A |
26 |
30 |
35 |
40 |
Min. Required circuit breaker size |
A |
30 |
40 |
40 |
50 |
Recemmended wire size |
AWG COPPER |
10 |
8 |
8 |
8 |
|
Maximum temperature increase |
@0.75 GPM |
49 |
65 |
65 |
87 |
above ambient water temp. |
@1.00 GPM |
37 |
49 |
49 |
65 |
|
@1.50 GPM |
25 |
33 |
33 |
44 |
Min. water flow to activate unit |
GPM / lmin |
0.29 / 1.1 |
0.29 / 1.1 |
Pressure loss in unit |
PSI / bar |
1.46 / 0.1 |
1.46 / 0.1 |
Weight |
LB / kg |
5.9 / 2.7 |
Nominal water volume |
Gal. |
0.13 / 0.51 |
Working pressure |
PSI / bar |
150 / 10 |
Tested to pressure |
PSI / bar |
300 / 20 |
Water connections |
1 / 2" NPT |
|